Guides · EN 1993-1-2

Section factor and fire protection thickness

How fast a steel section heats up, unprotected or protected, and how to choose the protection thickness.

The section factor Am/V

The section factor is the ratio between the surface exposed to fire Am and the volume V of the member, per unit length, in m−1. A slender section, with a large surface relative to its mass, heats up quickly; a massive one, slowly.

SectionAm/V
I/H section exposed on all sidesperimeter / area
I/H section exposed on 3 sides (under a slab)(perimeter − top flange width) / area
Hollow section exposed around its full perimeterouter perimeter / area ≈ 1 / t

EN 1993-1-2 (cl. 4.2.5, Table 4.2) gives the expressions for each case. The value should not be taken less than 10 m−1.

Shadow factor ksh

For I/H sections, the zones between the flanges receive less radiation. This is accounted for by the shadow factor (cl. 4.2.5.1):

ksh = 0.9 · [Am/V]b / [Am/V] I/H sections under nominal fire, eq. (4.26a); [Am/V]b is the box value of the section factor

For hollow sections exposed around the full perimeter, ksh = 1. Taking ksh = 1 is always conservative.

Heating of unprotected steel

The temperature increase of the steel over a time interval Δt (cl. 4.2.5.1):

Δθa,t = ksh · (Am/V) / (ca · ρa) · ḣnet · Δt eq. (4.25); Δt ≤ 5 s

Heating of protected steel

For a member with fire protection (cl. 4.2.5.2):

Δθa,t = (λp · Ap/V) / (dp · ca · ρa) · (θg,t − θa,t) / (1 + φ/3) · Δt − (eφ/10 − 1) · Δθg,t eq. (4.27); Δθa,t ≥ 0 if Δθg,t > 0; Δt ≤ 30 s
φ = (cp · ρp) / (ca · ρa) · dp · Ap/V heat capacity of the protection layer

How the protection thickness is determined

  1. Calculate the critical temperature θa,cr of the member.
  2. Take the required duration from the fire resistance class (for example 90 min for R 90).
  3. The required thickness is the smallest thickness dp for which the steel temperature at the end of the required duration stays below θa,cr.

The thermal properties of protection products come from their tests (the EN 13381 series), declared by the manufacturer. For intumescent paints, manufacturers usually provide thickness tables directly, by section factor and critical temperature.

Informative material summarising the provisions of EN 1993-1-2 and EN 1991-1-2. It does not replace the text of the standards, the protection manufacturer's documentation or verification by a qualified engineer.