EN 1993-1-2 · updated 3 November 2026

Validation of results against the published literature

A comparison of FireSolver results with the worked calculation examples in the published literature, to EN 1993-1-2.

Overview

To check that FireSolver results are correct, the calculation engine was compared with numerical examples published in the literature on the fire design of steel structures to EN 1993-1-2.

The analysis uses three reference sources. Each worked example is reproduced independently, with the same input data as in the original publication. The FireSolver results are compared with the published values, and the differences are shown and explained where needed.

The comparison covers:

For the examples calculated with the equations of EN 1993-1-2, the FireSolver results are very close to the published ones, and the differences are in general a few degrees Celsius or less. The larger differences come from values read from tables or nomograms, and the note under each table explains them.

Besides the comparisons with the published examples, the calculation engine is checked regularly by a set of more than 10,000 automated tests. The tests cover the sections in the catalogue of the application and the main checks that the application performs.

The reference source

Jean-Marc Franssen, Paulo Vila Real, Fire Design of Steel Structures. Eurocode 1: Actions on structures, Part 1-2. Eurocode 3: Design of steel structures, Part 1-2, 2nd edition, ECCS Eurocode Design Manuals, ECCS and Ernst & Sohn, 2015. ISBN 978-3-433-03143-8 (Ernst & Sohn), ISBN 978-92-9147-128-7 (ECCS).

The reference source is the ECCS (European Convention for Constructional Steelwork) manual for the fire design of steel structures to EN 1991-1-2 and EN 1993-1-2. The examples of chapters 4 and 5 are solved with the formulas of the standards, and some of them are also checked with the Elefir-EN program, described in chapter 8. This page compares the FireSolver results with those of the manual, for every example that the application covers. The example numbers (for example, 5.4) are those of the original manual.

Comparison method

The input data are those of the original examples: the properties of the section and of the steel, the design effects in the fire situation, the buckling lengths and the section factors. For all examples, γM,fi = 1.0, the ISO 834 standard fire curve and the convective heat transfer coefficient αc = 25 W/m²K are used.

In the tables, the "Book" column holds the reference value, that is the result published in the manual, with the same precision and rounding as in the original example. The "Method in the book" column states how this result was obtained: with an equation of the standard, with the Elefir-EN program or by reading a value from a table.

The "FireSolver" column holds the value calculated by the engine of the application, which is also used in the online calculators, in the version of 3 November 2026. An automated test reproduces these examples every week and reports any change in the results.

The "Difference" column holds the FireSolver result minus the reference value of the manual, with the number of decimals published in the original example.

1. Critical temperature

Temperatures in °C. N, M and V are the design effects in the fire situation. κ1 and κ2 are the adaptation factors for non-uniform temperature.

ExampleFailure modeBookFireSolverDifferenceMethod in the book
5.1: HE 200 A tension member, S275, N = 780 kNcross-section resistance576.1576.10.0eq. (4.22)
5.2: IPE 300 beam, S235, laterally restrained, M = 67.6 kNm, unprotected (κ1 = 0.7)cross-section resistance654653.80eq. (4.22)
5.2: same beam, protected (κ1 = 0.85)cross-section resistance624624.10eq. (4.22)
5.4: HE 180 B column, S275, ℓfi = 175 cm, N = 495 kNflexural buckling623623.20eq. (4.22)
5.5: HE 220 B column, S235, ℓfi = 140 cm, N = 980 kNflexural buckling565565.8+1eq. (4.22)
5.7: IPE 300 beam, S235, L = 5 m, M = 39.0 kNm, laterally restrainedcross-section resistance683683.10eq. (4.22)
5.7: same beam, laterally unrestrained, Mcr = 129.4 kNmlateral-torsional buckling519517.6−1eq. (4.22)
5.8: IPE 450, S235, L = 6 m, N = 136.5 kN, q = 15.89 kN/m (M = 71.5 kNm), laterally restrainedflexural buckling595595.20Table 3.1 (a)
5.8: same member, laterally unrestrained, Mcr = 347.2 kNmlateral-torsional buckling515515.40Table 3.1 (a)
5.9: HE 200 B column, S235, ℓfi,y = 150 cm, N = 800 kN, end moments ±50 kNm, buckling about z preventedflexural buckling552552.6+1Table 3.1 (a)
5.9: same columncross-section resistance to N and M (governs)516.5516.50.0Table 3.1 (a)
5.12: IPE 300 continuous beam, S235, intermediate support, M = 80.64 kNm, V = 80.64 kN, κ1 = 0.7, κ2 = 0.85cross-section resistance660.5660.50.0Table 3.1 (a)
5.12: same sectionshear699.4699.40.0Table 3.1 (a)
5.12: same sectionbending with shear (governs)656655.4−1Table 3.1 (a)
Ch. 8: HE 220 B column, S235, ℓfi,y = 300 cm, ℓfi,z = LLT = 150 cm, N = 130 kN, q = 13 kN/m (M = 14.625 kNm), Mcr = 3457.6 kNmfinal value752.5752.50.0Elefir-EN (a)

2. Heating of steel

The calculations use the ISO 834 standard fire curve, with a convective heat transfer coefficient αc = 25 W/m²K.

For unprotected steel members the modified section factor ksh · Am/V is used, and for protected members the section factor Ap/V. Both factors are in m⁻¹.

The protection materials are defined by the thermal conductivity λp (W/mK), the density ρp (kg/m³) and the specific heat cp (J/kgK).

The reference values of the manual do not include the heating delay caused by the moisture of the protection material. The FireSolver calculation model does not take this effect into account either.

Steel temperature at a given time

ExampleTimeBookFireSolverDifferenceMethod in the book
4.1: rectangular bar 200 × 50 mm, unprotected, 4 sides, ksh · Am/V = 5030 min690691.5+2Elefir-EN
4.2: circular hollow section Ø220 × 5, unprotected, ksh · Am/V = 20060 min942942.00table, Annex A.4 (b)
4.3: HE 200 A, unprotected, 4 sides, ksh · Am/V = 130.530 min802803.2+1eq. (4.25)
5.4: HE 180 B, unprotected, 4 sides, ksh · Am/V = 99.230 min766767.4+1table, Annex A.4 (b)
4.6: IPE 300, fibre-cement board encasement 20 mm (0.15 / 800 / 1200), 4 sides, Ap/V = 167.360 min451453.1+2Elefir-EN

Time to reach a given temperature

ExampleSteel temperatureBook (min)FireSolver (min)DifferenceMethod in the book
4.5: HE 220 B, gypsum board encasement 20 mm (0.20 / 800 / 1700), 4 sides, Ap/V = 96.7559 °C98.995.00−3.9Elefir-EN (c)
5.1: HE 200 A, unprotected, 4 sides, ksh · Am/V = 130.4576.1 °C14.0813.25−0.83table, Annex A.4 (b)
5.2: IPE 300, unprotected, 3 sides, ksh · Am/V = 125.5654 °C1816.75−1table, Annex A.4 (b)
5.4: HE 180 B, unprotected, 4 sides, ksh · Am/V = 99.2623 °C17.417.33−0.1table, Annex A.4 (b)
5.5: HE 220 B, gypsum board encasement 20 mm (0.20 / 800 / 1700), 4 sides, Ap/V = 96565 °C9996.50−3table, Annex A.5 (b)
Ch. 8: HE 220 B, unprotected, 4 sides, Am/V = 139.6752.5 °C30.3530.33−0.02Elefir-EN
Ch. 8: same column, contour mineral fibre 5 mm (0.12 / 300 / 1200), Ap/V = 139.6752.5 °C67.6767.00−0.67Elefir-EN (d)

3. Protection thickness

ExampleProtection, requirementBook (mm)FireSolver (mm)DifferenceMethod in the book
4.4: IPE 300, 3 sides, Ap/V = 139.4, θa,cr = 654 °Cfibre-cement board encasement (0.15 / 800 / 1200), R 9014.315.5+1.2table, Annex A.5 (e)

For the column of chapter 8, the book chooses 5 mm of mineral fibre and checks the time (table above). The minimum thickness for R 60 given by FireSolver is 4.5 mm.

4. Other published sources

Worked examples from two other published sources are reproduced, with the input data of the original examples. The section properties and section factors are taken from the FireSolver catalogue, and the values match those published in the reference sources.

Critical temperature

Temperatures in °C, γM,fi = 1.0.

ExampleFailure modeSourceFireSolverDifferenceNote
[J] ex. 3: IPE 400, S355, Mfi,Ed = 74.3 kNm, unprotected (κ1 = 0.7)cross-section resistance812812.00
[J] ex. 3: IPE 400, protected (κ1 = 0.85)cross-section resistance783782.80
[J] ex. 3: IPE 400, Vfi,Ed = 49.3 kNshear916.3915.4−0.9(f)
[J] ex. 2: HEB 340 column, S355, ℓfi = 216.75 cm, Nfi,Ed = 2161.9 kNflexural buckling598.5597.7−0.8(h)
[H] 2.2: HEA 550, S235, Mfi,Ed = 351.4 kNm, κ1 = 0.7cross-section resistance708706.3−2(f)
[H] 2.2: HEB 550, S235, same loadcross-section resistance736734.9−1(f)
[H] 2.2: HEA 550, S355, same loadcross-section resistance768768.30
[H] 2.2: HEA 550, S235, continuous beam, Mfi,Ed = 242.4 kNm, κ2 = 0.85cross-section resistance789786.6−2(f)
[H] 2.3: HEA 400, S235, Mfi,Ed = 232.8 kNm, κ1 = 0.85cross-section resistance649649.9+1
[H] 2.5: HEA 400, S235, Mfi,Ed = 233 kNm, λ̄LT = 0.80lateral-torsional buckling500502.6+3(g)

Heating of unprotected steel

The calculations use the ISO 834 standard fire curve and the convective heat transfer coefficient αc = 25 W/m²K.

The reference source gives the steel temperature at a given time, and FireSolver calculates the time needed to reach that temperature. The modified section factor ksh · Am/V is in m⁻¹.

ExampleSteel temperatureSourceFireSolverDifferenceNote
[J] ex. 1: HEB 340, 4 sides, ksh · Am/V = 67.4730 °C30 min 0 s29 min 30 s−30 snomogram
[J] ex. 2: HEB 340, 4 sides598.5 °C20 min 18 s20 min 15 s−3 sElefir-EN, 20.3 min
[J] ex. 3: IPE 400, 3 sides, ksh · Am/V = 104.4812 °C33 min 0 s33 min 5 s+5 snomogram
[H] 2.2: HEA 550, 3 sides, ksh · Am/V = 59721 °C30 min 0 s30 min 15 s+15 s
[H] 2.2: HEB 550, 3 sides, ksh · Am/V = 50693 °C30 min 0 s30 min 20 s+20 s

Protection thickness

Standard fire curve ISO 834, with the critical temperature of the source. Thicknesses in mm.

ExampleProtection, requirementSourceFireSolverDifference
[J] ex. 1: HEB 340, 4 sides, θa,cr = 598.5 °Cgypsum board encasement 0.20 / 800 / 1700, R 9013.714.0+0.3
[H] 2.3: HEA 400, 3 sides, θa,cr = 649 °Ccontour spray 0.12 / 550 / 1100, R 606.16.0−0.1
[H] 2.5: HEA 400, 3 sides, θa,cr = 500 °Ccontour spray 0.12 / 550 / 1100, R 6010.810.5−0.3

The sources read the modified section factor (Ap/V)(λp/dp) from a nomogram and calculate the thickness from it. [J] then corrects the thickness for the heat capacity of the protection; in [H] the correction is 3-5% and the book neglects it. FireSolver integrates eq. (4.27) in 30 s steps and rounds the thickness up to 0.5 mm.

5. Automated tests

Besides the published examples, more than 10,000 automated test cases check the calculation engine. They cover every section in the catalogue of the application, several steel grades and several load levels:

Each case compares the engine result with a reference value calculated independently of the application code. The examples on this page are also part of the tests. The full set runs every week, and a subset runs each time the calculation engine is released. A test fails when a result moves outside its tolerance: 5 s for unprotected heating, 30 s for protected heating and 0.01-0.5 °C for critical temperatures.

What the comparison does not cover

Information about how the application is checked. It does not replace the text of the standard, the National Annex or verification by a qualified engineer.