Hollow sections are common in single-storey halls, canopies and exposed structures. The guide uses the names from the section catalogue of the app: SHS for square hollow sections, RHS for rectangular hollow sections and CHS for circular hollow sections.
1. What is different about a hollow section
- The section is closed. The torsional stiffness is high, so square and circular hollow sections (SHS, CHS) have no lateral-torsional buckling. An RHS in bending about the strong axis can buckle laterally, but this usually does not govern.
- SHS and CHS have the same radius of gyration about both axes. There is no weak axis, as there is for I and H sections.
- The wall has the same thickness all around and the section is convex. The whole perimeter receives the same heat flux, with no shaded zones, so the shadow factor is ksh = 1 (EN 1993-1-2, 4.2.5.1, Note 1).
2. Section factor
For a thin wall of thickness t, the exposed perimeter per unit length is almost equal to the area divided by t. For this reason Am/V depends almost only on the wall thickness: Am/V ≈ 1 / t. Two hollow sections with the same wall thickness heat up almost at the same rate, whatever their outside dimensions.
The values for exposure on 4 sides, from the section catalogue of the app, compared with 1 / t:
| Section | t (mm) | Am/V (m−1) | 1 / t (m−1) |
|---|---|---|---|
| SHS 100×100×5 | 5 | 207.0 | 200 |
| SHS 150×150×8 | 8 | 129.2 | 125 |
| SHS 200×200×10 | 10 | 103.3 | 100 |
| SHS 200×200×12.5 | 12.5 | 83.4 | 80 |
| RHS 250×150×8 | 8 | 128.3 | 125 |
| RHS 250×150×10 | 10 | 102.8 | 100 |
| CHS 168.3×8 | 8 | 131.3 | 125 |
| CHS 219.1×10 | 10 | 104.7 | 100 |
| CHS 323.9×12.5 | 12.5 | 83.6 | 80 |
For an HEB section, unprotected steel heats up with ksh · Am/V. For an HEB 200 exposed on 4 sides, Am/V = 147.4 m−1, [Am/V]b = 102.5 m−1 and ksh = 0.9 · 102.5 / 147.4 = 0.626, so the value used is 92.2 m−1. A hollow section has no such reduction: the value used is Am/V itself. Details are in the guide on the section factor.
For a hollow section placed against a wall (3 sides exposed), the side against the wall is removed from the perimeter and Am/V is lower. The app has the values for 3 and 4 sides.
3. Cross-section class in fire
In fire, ε = 0.85 · √(235 / fy) (cl. 4.2.2). For S355, ε = 0.692. The walls of an SHS or RHS in compression are internal parts: the flat width is c = b − 3t, and the limits are 33ε, 38ε and 42ε. For a circular hollow section, d/t is compared with 50ε², 70ε² and 90ε².
| Section, S355, compression | Ratio | Limits for classes 1 / 2 / 3 | Class in fire |
|---|---|---|---|
| SHS 200×200×5 | c/t = 37.0 | 22.8 / 26.3 / 29.0 | 4 |
| SHS 200×200×6.3 | c/t = 28.7 | 22.8 / 26.3 / 29.0 | 3 |
| SHS 200×200×8 | c/t = 22.0 | 22.8 / 26.3 / 29.0 | 1 |
| SHS 200×200×10 | c/t = 17.0 | 22.8 / 26.3 / 29.0 | 1 |
| RHS 250×150×8 (250 mm side) | c/t = 28.3 | 22.8 / 26.3 / 29.0 | 3 |
| CHS 219.1×10 | d/t = 21.9 | 23.9 / 33.5 / 43.0 | 1 |
| CHS 219.1×6.3 | d/t = 34.8 | 23.9 / 33.5 / 43.0 | 3 |
| CHS 323.9×6.3 | d/t = 51.4 | 23.9 / 33.5 / 43.0 | 4 |
- Hollow sections with thin walls easily move to class 3 or 4 in fire. An SHS 200×200×6.3 in S355 is class 2 at normal temperature (ε = 0.814, the class 2 limit is 30.9) and class 3 in fire.
- For class 4, EN 1993-1-2 recommends a critical temperature of 350 °C when no detailed calculation is made. The app does not check class 4 sections and shows a message.
- For class 3, the elastic modulus Wel is used in bending. The limits for all steel grades are in the guide on cross-section classes in fire.
4. Example: SHS and HEB of similar weight under the same axial force
A column pinned at both ends, for example in a single-storey hall, with length L = 4.00 m and ℓfi = 4.00 m about both axes. The axial force in fire is Nfi,Ed = 600 kN, γM,fi = 1.0, steel S355 (fy = 355 N/mm²), exposure on 4 sides, ISO 834 standard curve. Two sections are compared:
| Quantity | HEB 200 | SHS 200×200×10 |
|---|---|---|
| A | 78.08 cm² | 74.9 cm² |
| Mass | 61.3 kg/m | 58.8 kg/m |
| Iy / Iz | 5696 / 2003 cm⁴ | 4471 / 4471 cm⁴ |
| Class in fire | 1 | 1 |
| A · fy | 2771.8 kN | 2659.0 kN |
The slenderness, with Ncr = π² · E · I / ℓfi² and λ̄ = √(A · fy / Ncr):
For each temperature θ, calculate λ̄θ = λ̄ · √(ky,θ / kE,θ), then χfi, the degree of utilisation μ0 = Nfi,Ed / (χfi · A · fy / γM,fi) and, from eq. (4.22), a new temperature. Repeat until the temperature no longer changes. The method is the one in the guide on steel columns.
HEB 200, buckling about the weak axis z:
| θ (°C) | ky,θ / kE,θ | λ̄z,θ | χz,fi | μ0 | New θ (°C) |
|---|---|---|---|---|---|
| 20.0 | 1.000 | 1.034 | 0.474 | 0.456 | 599.2 |
| 599.2 | 1.513 | 1.271 | 0.372 | 0.582 | 559.6 |
| 559.6 | 1.394 | 1.220 | 0.392 | 0.552 | 568.5 |
| 568.5 | 1.414 | 1.229 | 0.389 | 0.557 | 566.9 |
| 566.9 | 1.410 | 1.227 | 0.389 | 0.556 | 567.2 |
| 567.2 | 1.411 | 1.228 | 0.389 | 0.556 | 567.1 |
About the strong axis, the same iteration gives 638.6 °C, so the weak axis governs: θa,cr = 567.1 °C.
SHS 200×200×10, the same value about both axes:
| θ (°C) | ky,θ / kE,θ | λ̄θ | χfi | μ0 | New θ (°C) |
|---|---|---|---|---|---|
| 20.0 | 1.000 | 0.678 | 0.660 | 0.342 | 644.0 |
| 644.0 | 1.579 | 0.851 | 0.567 | 0.398 | 620.5 |
| 620.5 | 1.541 | 0.841 | 0.572 | 0.394 | 622.0 |
| 622.0 | 1.543 | 0.842 | 0.572 | 0.395 | 621.9 |
For the SHS, θa,cr = 621.9 °C, which is 54.8 °C above the HEB 200. The difference comes from the weak axis of the HEB section: with almost the same area, the hollow section has a slenderness of 0.678 about both axes, compared with 1.034 about the z axis of the HEB.
The time to the critical temperature without protection, from eq. (4.25):
| Quantity | HEB 200 | SHS 200×200×10 |
|---|---|---|
| θa,cr | 567.1 °C | 621.9 °C |
| ksh · Am/V | 0.626 · 147.4 = 92.2 m−1 | 1 · 103.3 = 103.3 m−1 |
| Time without protection | 15.8 min | 16.9 min |
The hollow section heats up slightly faster, but its critical temperature is higher. The result is almost the same: both sections reach only R 15 without protection.
5. Protection
For an HEB section, a board box has a smaller perimeter than the section, so Ap/V is lower than for a spray applied on the contour. For an SHS or RHS, the box follows the outline of the section, so boards and sprays have the same Ap/V = Am/V.
The minimum thickness from eq. (4.27) for the example above, with gypsum boards in a box (λp = 0.20 W/mK, ρp = 800 kg/m³, cp = 1700 J/kgK) and with a vermiculite cement spray on the contour (λp = 0.12 W/mK, ρp = 350 kg/m³, cp = 1200 J/kgK):
| Section and protection | Ap/V | R 30 | R 60 | R 90 | R 120 |
|---|---|---|---|---|---|
| HEB 200, gypsum boards in a box | 102.5 m−1 | 5.5 mm | 12.5 mm | 19.5 mm | 26.0 mm |
| SHS 200×200×10, gypsum boards in a box | 103.3 m−1 | 4.5 mm | 10.5 mm | 16.5 mm | 22.5 mm |
| HEB 200, spray on the contour | 147.4 m−1 | 5.0 mm | 12.0 mm | 19.0 mm | 26.5 mm |
| SHS 200×200×10, spray on the contour | 103.3 m−1 | 3.0 mm | 7.0 mm | 11.5 mm | 16.5 mm |
- With boards in a box, Ap/V is almost the same for the two sections. The hollow section needs 3 mm less for R 90 because of its higher critical temperature.
- With a spray on the contour, the hollow section has a 30% lower Ap/V and a higher critical temperature. For R 90 it needs 11.5 mm, compared with 19 mm for the HEB 200.
- The values are valid if the properties declared by the manufacturer are at least as good as the ones used here. Other materials are compared in the guide on boards and sprays.
Informative material summarising the provisions of EN 1993-1-2. It does not replace the text of the standard, the National Annex or verification by a qualified engineer.