Guides · EN 1993-1-2

Worked example: IPE 300 beam with lateral-torsional buckling

The fire check of a beam with a laterally unrestrained compression flange, step by step, from the section class to the protection thickness.

Input data

QuantityValue
h × b × tw × tf × r300 × 150 × 7.1 × 10.7 × 15 mm
A53.81 cm²
Wpl,y628.4 cm³
Iz / It603.8 / 20.12 cm⁴
Iw125 900 cm⁶
Am/V (contour, 3 sides)187.7 m−1
[Am/V]b (box, 3 sides)139.4 m−1

1. Cross-section class

ε = 0.85 · √(235 / 235) = 0.850

The section is Class 1, so Wpl,y is used. Details in the guide on cross-section classes in fire.

2. Cross-section resistance and shear

Without lateral-torsional buckling, the moment resistance at 20 °C, with the adaptation factors, is:

Mfi,0,Rd = Wpl,y · fy / (κ1 · κ2 · γM,fi) = 147.67 / 0.85 = 173.73 kNm    μ0 = 39.0 / 173.73 = 0.225

Eq. (4.22) gives θa,cr = 707.6 °C.

Av = 25.68 cm²    Vfi,0,Rd = Av · fy / (√3 · γM,fi) = 348.4 kN    μ0 = 31.2 / 348.4 = 0.090

For shear, θa,cr = 845.8 °C. At the final critical temperature the shear force is below half the shear resistance, so the moment resistance is not reduced.

3. Elastic critical moment Mcr and slenderness λ̄LT

For a uniformly distributed load on a simply supported beam, with k = kw = 1.0: C1 = 1.132 and C2 = 0.459. The load is applied at the shear centre, so zg = 0 and the C2 term drops out of the formula in the guide on beams:

π² · E · Iz / L² = 500.6 kN    Iw / Iz = 208.5 cm²    L² · G · It / (π² · E · Iz) = 324.6 cm²
Mcr = 1.132 · 500.6 · √(208.5 + 324.6) = 130.84 kNm
λ̄LT = √(Wpl,y · fy / Mcr) = √(147.67 / 130.84) = 1.062    α = 0.65 · √(235 / 235) = 0.65

4. Critical temperature from lateral-torsional buckling

The critical temperature is found iteratively. For a temperature θ, compute the slenderness λ̄LT,θ = λ̄LT · √(ky,θ / kE,θ), the factor χLT,fi and the moment Mb,fi,0,Rd = χLT,fi · Wpl,y · fy / γM,fi. The degree of utilisation μ0 = My,fi,Ed / Mb,fi,0,Rd gives a new temperature through eq. (4.22). Repeat until the temperature stops changing. The factors κ1 and κ2 do not enter this calculation.

θ (°C)ky,θ / kE,θλ̄LT,θφLT,θχLT,fiMb,fi,0,Rd (kNm)μ0New θ (°C)
20.01.0001.0621.4100.42863.220.617549.4
549.41.3721.2451.6790.35652.630.741514.0
514.01.3171.2191.6390.36653.990.722519.4
519.41.3241.2221.6440.36453.810.725518.7
518.71.3231.2221.6440.36553.840.724518.8

At convergence ky,θ = 0.722 and kE,θ = 0.546, interpolated from Table 3.1. Lateral-torsional buckling governs: θa,cr = 518.8 °C, well below the 707.6 °C of the cross-section resistance.

5. Time without protection

ksh = 0.9 · 139.4 / 187.7 = 0.668    ksh · Am/V = 125.4 m−1

Integrating eq. (4.25) under the ISO 834 curve, the unprotected steel reaches 518.8 °C after 11.8 minutes. The unprotected beam does not achieve even R 15, so it needs protection for R 60.

6. Protection thickness

Sprayed mineral fibre protection on the contour (λp = 0.12 W/mK, ρp = 300 kg/m³, cp = 1200 J/kgK), Ap/V = 187.7 m−1. With dp = 10 mm, the steel reaches 518.8 °C after 38.5 minutes: the beam achieves R 30, but not R 60.

With eq. (4.27), the minimum thickness that keeps the steel below 518.8 °C:

ClassR 30R 60R 90R 120
Required dp7.5 mm17.0 mm27.0 mm36.5 mm

R 60 needs 17 mm, provided the properties declared by the manufacturer are at least as good as the values used here. A comparison with other materials is in the guide on boards and sprays.

What affects the result

The same beam under the same actions, with one change to the input data above:

ChangeMcrθa,crdp for R 60
The example above130.8 kNm518.8 °C17.0 mm
Top flange restrained by the slab (no lateral-torsional buckling)-707.6 °C8.5 mm
Ends prevented from rotating laterally (k = 0.5; C1 = 0.972)224.7 kNm566.6 °C14.5 mm
Uniform moment over the full length (C1 = 1.00)115.6 kNm503.6 °C18.0 mm
Load applied on the top flange (zg = +150 mm)97.5 kNm462.9 °C20.5 mm

Informative material summarising the provisions of EN 1993-1-2. It does not replace the text of the standard, the National Annex or verification by a qualified engineer.

Rerun the example with your own data, with a PDF report.

Get started

Free online calculator, no account needed.