Input data
- IPE 300 beam in S235, fy = 235 N/mm², E = 210 000 N/mm², G = 80 770 N/mm².
- Simply supported beam, span L = 5.00 m, no intermediate lateral restraints: LLT = 5.00 m. The top flange is not laterally restrained by the slab, so lateral-torsional buckling is checked.
- Uniformly distributed load qfi,d = 12.48 kN/m, applied at the shear centre: My,fi,Ed = qfi,d · L² / 8 = 39.0 kNm, Vz,fi,Ed = qfi,d · L / 2 = 31.2 kN; γM,fi = 1.0.
- Three-sided exposure, with a concrete slab on the fourth side, ISO 834 standard curve, required class R 60.
- Protected beam: κ1 = 0.85, κ2 = 1.00.
| Quantity | Value |
|---|---|
| h × b × tw × tf × r | 300 × 150 × 7.1 × 10.7 × 15 mm |
| A | 53.81 cm² |
| Wpl,y | 628.4 cm³ |
| Iz / It | 603.8 / 20.12 cm⁴ |
| Iw | 125 900 cm⁶ |
| Am/V (contour, 3 sides) | 187.7 m−1 |
| [Am/V]b (box, 3 sides) | 139.4 m−1 |
1. Cross-section class
- Flange: c = (150 − 7.1 − 2·15) / 2 = 56.45 mm; c/tf = 5.28 ≤ 9ε = 7.65, so Class 1.
- Web (bending): c = 300 − 2·10.7 − 2·15 = 248.6 mm; c/tw = 35.0 ≤ 72ε = 61.2, so Class 1.
The section is Class 1, so Wpl,y is used. Details in the guide on cross-section classes in fire.
2. Cross-section resistance and shear
Without lateral-torsional buckling, the moment resistance at 20 °C, with the adaptation factors, is:
Eq. (4.22) gives θa,cr = 707.6 °C.
For shear, θa,cr = 845.8 °C. At the final critical temperature the shear force is below half the shear resistance, so the moment resistance is not reduced.
3. Elastic critical moment Mcr and slenderness λ̄LT
For a uniformly distributed load on a simply supported beam, with k = kw = 1.0: C1 = 1.132 and C2 = 0.459. The load is applied at the shear centre, so zg = 0 and the C2 term drops out of the formula in the guide on beams:
4. Critical temperature from lateral-torsional buckling
The critical temperature is found iteratively. For a temperature θ, compute the slenderness λ̄LT,θ = λ̄LT · √(ky,θ / kE,θ), the factor χLT,fi and the moment Mb,fi,0,Rd = χLT,fi · Wpl,y · fy / γM,fi. The degree of utilisation μ0 = My,fi,Ed / Mb,fi,0,Rd gives a new temperature through eq. (4.22). Repeat until the temperature stops changing. The factors κ1 and κ2 do not enter this calculation.
| θ (°C) | ky,θ / kE,θ | λ̄LT,θ | φLT,θ | χLT,fi | Mb,fi,0,Rd (kNm) | μ0 | New θ (°C) |
|---|---|---|---|---|---|---|---|
| 20.0 | 1.000 | 1.062 | 1.410 | 0.428 | 63.22 | 0.617 | 549.4 |
| 549.4 | 1.372 | 1.245 | 1.679 | 0.356 | 52.63 | 0.741 | 514.0 |
| 514.0 | 1.317 | 1.219 | 1.639 | 0.366 | 53.99 | 0.722 | 519.4 |
| 519.4 | 1.324 | 1.222 | 1.644 | 0.364 | 53.81 | 0.725 | 518.7 |
| 518.7 | 1.323 | 1.222 | 1.644 | 0.365 | 53.84 | 0.724 | 518.8 |
At convergence ky,θ = 0.722 and kE,θ = 0.546, interpolated from Table 3.1. Lateral-torsional buckling governs: θa,cr = 518.8 °C, well below the 707.6 °C of the cross-section resistance.
5. Time without protection
Integrating eq. (4.25) under the ISO 834 curve, the unprotected steel reaches 518.8 °C after 11.8 minutes. The unprotected beam does not achieve even R 15, so it needs protection for R 60.
6. Protection thickness
Sprayed mineral fibre protection on the contour (λp = 0.12 W/mK, ρp = 300 kg/m³, cp = 1200 J/kgK), Ap/V = 187.7 m−1. With dp = 10 mm, the steel reaches 518.8 °C after 38.5 minutes: the beam achieves R 30, but not R 60.
With eq. (4.27), the minimum thickness that keeps the steel below 518.8 °C:
| Class | R 30 | R 60 | R 90 | R 120 |
|---|---|---|---|---|
| Required dp | 7.5 mm | 17.0 mm | 27.0 mm | 36.5 mm |
R 60 needs 17 mm, provided the properties declared by the manufacturer are at least as good as the values used here. A comparison with other materials is in the guide on boards and sprays.
What affects the result
The same beam under the same actions, with one change to the input data above:
| Change | Mcr | θa,cr | dp for R 60 |
|---|---|---|---|
| The example above | 130.8 kNm | 518.8 °C | 17.0 mm |
| Top flange restrained by the slab (no lateral-torsional buckling) | - | 707.6 °C | 8.5 mm |
| Ends prevented from rotating laterally (k = 0.5; C1 = 0.972) | 224.7 kNm | 566.6 °C | 14.5 mm |
| Uniform moment over the full length (C1 = 1.00) | 115.6 kNm | 503.6 °C | 18.0 mm |
| Load applied on the top flange (zg = +150 mm) | 97.5 kNm | 462.9 °C | 20.5 mm |
- The lateral restraints change the result the most: a top flange restrained by the slab removes lateral-torsional buckling and halves the protection thickness.
- The moment distribution enters through C1: under a uniform moment, Mcr is 12% lower than under the uniformly distributed load.
- A load applied on the top flange destabilises the beam: Mcr drops by 25% and the protection grows from 17.0 to 20.5 mm.
Informative material summarising the provisions of EN 1993-1-2. It does not replace the text of the standard, the National Annex or verification by a qualified engineer.