Guides · EN 1993-1-2

Worked example: HEB 240 column in compression and bending

The fire check of a frame column under axial force and bending, step by step, from the section class to the protection thickness.

Input data

QuantityValue
h × b × tw × tf × r240 × 240 × 10 × 17 × 21 mm
A106.0 cm²
Iy / Iz11 260 / 3 923 cm⁴
Wpl,y1 053 cm³
It / Iw102.7 cm⁴ / 486 900 cm⁶
Am/V (contour, 4 sides)130.6 m−1
[Am/V]b (box, 4 sides)90.6 m−1

1. Cross-section class

ε = 0.85 · √(235 / 355) = 0.692

The section is Class 1, so Wpl,y is used. Details in the guide on cross-section classes in fire.

2. Slenderness about both axes

Braced frame, intermediate storey, a fire compartment on each storey: ℓfi = 0.5 · L = 2.00 m about both axes (clause 4.2.3.2(4)).

A · fy = 3 763 kN    Ncr,y = π² · E · Iy / ℓfi² = 58 344 kN    λ̄y = √(A · fy / Ncr,y) = 0.254
Ncr,z = π² · E · Iz / ℓfi² = 20 327 kN    λ̄z = √(A · fy / Ncr,z) = 0.430

For lateral-torsional buckling the length is the distance between lateral restraints (the floors), LLT = L = 4.00 m, with k = kw = 1.0; the reduction in clause 4.2.3.2(4) applies only to flexural buckling. The moment is uniform, so C1 = 1.00, and the formula in the guide on beams gives:

π² · E · Iz / LLT² = 5 081.8 kN    Iw / Iz = 124.1 cm²    LLT² · G · It / (π² · E · Iz) = 163.2 cm²
Mcr = 1.00 · 5 081.8 · √(124.1 + 163.2) = 861.43 kNm
λ̄LT = √(Wpl,y · fy / Mcr) = √(373.81 / 861.43) = 0.659    α = 0.65 · √(235 / 355) = 0.529

3. The interaction equations

Clause 4.2.3.5 requires two checks, each at the steel temperature θ. With no moment about the minor axis, the Mz,fi,Ed term drops out:

(4.21a)   Nfi,Ed / (χmin,fi · A · ky,θ · fy / γM,fi) + ky · My,fi,Ed / (Wpl,y · ky,θ · fy / γM,fi) ≤ 1
(4.21b)   Nfi,Ed / (χz,fi · A · ky,θ · fy / γM,fi) + kLT · My,fi,Ed / (χLT,fi · Wpl,y · ky,θ · fy / γM,fi) ≤ 1

The moment diagram enters through the equivalent uniform moment factor: for ψ = 1, βM,y = βM,LT = 1.8 − 0.7 · ψ = 1.10. The interaction factors are:

μy = (2 · βM,y − 5) · λ̄y,θ + 0.44 · βM,y + 0.29 ≤ 0.8    ky = 1 − μy · Nfi,Ed / (χy,fi · A · ky,θ · fy / γM,fi) ≤ 3
μLT = 0.15 · λ̄z,θ · βM,LT − 0.15 ≤ 0.9    kLT = 1 − μLT · Nfi,Ed / (χz,fi · A · ky,θ · fy / γM,fi) ≤ 1

With ky,θ taken out as a common factor, each equation becomes μ0 ≤ ky,θ, where μ0 is the sum of the terms computed with fy at 20 °C. For a temperature θ, compute the slenderness λ̄θ = λ̄ · √(ky,θ / kE,θ), the factors χfi and k, then μ0 and, from eq. (4.22), a new temperature. Repeat until the temperature stops changing.

4. Critical temperature from eq. (4.21a)

At 20 °C: μy = (2 · 1.10 − 5) · 0.254 + 0.44 · 1.10 + 0.29 = 0.063, ky = 0.985 and μ0 = 800 / (0.790 · 3 763) + 0.985 · 40 / 373.81 = 0.269 + 0.105 = 0.375.

θ (°C)ky,θ / kE,θλ̄y,θχy,fiλ̄z,θχz,fikyμ0New θ (°C)
20.01.0000.2540.8750.4300.7900.9850.375629.9
629.91.5550.3170.8450.5360.7351.0710.404618.4
618.41.5380.3150.8460.5340.7371.0640.402618.9
618.91.5390.3150.8460.5340.7371.0640.402618.9

The minor axis governs, through χmin,fi = χz,fi: eq. (4.21a) gives θa,cr = 618.9 °C. The values of ky,θ and kE,θ are interpolated from Table 3.1.

5. Critical temperature from eq. (4.21b), with lateral-torsional buckling

At 20 °C: μLT = 0.15 · 0.430 · 1.10 − 0.15 = −0.079. The negative value gives kLT above 1, so kLT = 1.000 is used (and at every temperature in the table), and μ0 = 800 / (0.790 · 3 763) + 1.000 · 40 / (0.671 · 373.81) = 0.269 + 0.160 = 0.429.

θ (°C)ky,θ / kE,θλ̄LT,θχLT,fiλ̄z,θχz,fikLTμ0New θ (°C)
20.01.0000.6590.6710.4300.7901.0000.429609.0
609.01.5260.8140.5870.5320.7381.0000.470594.4
594.41.4940.8050.5910.5260.7411.0000.468595.3
595.31.4970.8060.5910.5260.7411.0000.468595.2

Lateral-torsional buckling governs: θa,cr = 595.2 °C, below the 618.9 °C from eq. (4.21a).

6. Time without protection

ksh = 0.9 · 90.6 / 130.6 = 0.624    ksh · Am/V = 81.5 m−1

Integrating eq. (4.25) under the ISO 834 curve, the unprotected steel reaches 595.2 °C after 18.1 minutes. The unprotected column achieves only R 15, so it needs protection for R 90.

7. Protection thickness

Gypsum board protection as a box (λp = 0.20 W/mK, ρp = 800 kg/m³, cp = 1700 J/kgK), Ap/V = 90.6 m−1. With eq. (4.27), the minimum thickness that keeps the steel below 595.2 °C:

ClassR 30R 60R 90R 120
Required dp4.5 mm10.5 mm16.5 mm22.5 mm

R 90 needs 16.5 mm, provided the properties declared by the manufacturer are at least as good as the values used here. A comparison with other materials is in the guide on boards and sprays.

What affects the result

The same column, with one change to the input data above:

ChangeMcrθ from (4.21a)θ from (4.21b)dp for R 90
The example above861.4 kNm618.9 °C595.2 °C16.5 mm
Moment at one end only (ψ = 0; βM = 1.80; C1 = 1.879)1 618.6 kNm639.9 °C605.1 °C16.0 mm
Equal end moments of opposite sign (ψ = −1; βM = 2.50; C1 = 2.752)2 370.7 kNm646.0 °C610.5 °C16.0 mm
Double the moment, My,fi,Ed = 80 kNm861.4 kNm582.1 °C544.9 °C19.0 mm
Higher axial force, Nfi,Ed = 1200 kN861.4 kNm572.4 °C554.1 °C18.5 mm
Top storey, ℓfi = 0.7 · L = 2.80 m about both axes861.4 kNm594.1 °C580.3 °C17.0 mm

Informative material summarising the provisions of EN 1993-1-2. It does not replace the text of the standard, the National Annex or verification by a qualified engineer.